Rated voltage 127kV/220kVXLPE insulated corrugated aluminum PE(PVC) sheathed power cable products introduction

  • Pictures
  • Introduction
  • Parameters

1 Product Implementation standards

50/66kV: IEC 60840
64/110 kV: GB/T11017 IEC 60840
76/132 kV: AS/NZS 1429.2
127/220 kV: GB/Z 18890 IEC 62067

2 The use of conditions:

2.1 Use Occasions

Suitable for laying indoors, in tunnel, pipeline and other places, can bear the pressure, and can bear a certain traction, the cable has a reliable radial water resistance function. ZR-YJLW02-Z, ZR-YJLW02, applicable to the installation of fire requirements of the premises, FY-YJLW03-Z, FY-YJLW02-Z suitable for the installation of the requirements of the site where the ants;

2.2Rated Voltage in Power System

Allowable rated voltage value of cable U0、U、Um is as follows:

Table:
U0:The rated voltage (phase voltage) between a conductor and a shield  or a metal shield for the design of a cable.
U:Rated voltage (line  voltage) between conductors used in cable design
Um:Equipment maximum voltage the maximum value of the highest voltage  system using equipment

2.3 Frequency: 49 ~ 61Hz
2.4 The maximum rated operating  temperature of the cable conductor: 90.
2.5 The maximum rated operating temperature  of the short circuit of the cable conductor (short circuit time is not more  than 5S): 250.
2.6 System neutral grounding mode:
66kV cable: grounding through arc suppression coil.
110 ~ 220kV cable: direct grounding system.

Cable type and description

3.1 Code

220kv_02.jpg

3.2 Type

3.3 Product Description

The cable model is composed of characteristic code, insulation, conductor, metal sheath, non-metallic sheath , water blocking structure and rated voltage), specifications (core, the nominal cross-section) and standard code.

For example:
3.3.1   ZC-YJ LW 02-Z-64/110KV-1*1000
ZC……….Flame retardant C class
YJ……….XLPE insulated(copper)
LW……….Corrugated  aluminum sheath
02……….PVC  outer sheath
Z……….Water  blocking
64/110K……….Voltage  grade
1*1000……….Single core and conductor nominal cross-section
Cable specification: Rate voltage  64/110kV,single core , copper conductor nominal cross section 1200mm2, XLPE insulated corrugated aluminum sheathed longitudinal blocking water flame retardant class C PVC sheathed power cable.
3.3.2   FY-YJ L LW 03-Z-127/220KV-1*2500
FY……….Anti-termites
YJ……….XLPE insulated
L……….aluminum  core
LW……….Corrugated  aluminum sheath
03……….PE  outer sheath
Z……….Longitudinal  water proof
127/220KV……….Voltage grade
1*2500……….Single core and conductor nominal cross-section
Cable specification: Rate voltage  127/220kV, single core, Aluminum conductor nominal cross section 2500mm2, XLPE insulated corrugated  aluminum sheathed longitudinal water proof flame retardant PE sheathed power  cable.

4 Product Structure

4.1 Product Structure Diagrams

Specification  Model:YJLW03-127/220KV-1*2500mm2

Specification  Model:YJLW03-127/220KV-1*1600mm2

4.2 Product Structure

4.2.1 Conductor

Conductor  material using copper core tight circular conductor or sector split conductor.  When the nominal cross-sectional area of the conductor is greater than or equal  to 800mm2, the  split conductor structure should be adopted, and the structure and the DC  resistance should be in accordance with the provisions of GB/Z 18890.

Nominal cross section 630mm2 and following copper conductor cables line shall not be less than 53 root, nominal cross-sectional area of 800 mm2 to 1600mm2  copper cable segmentation conductor line shall not be less than 170 root, the  nominal section 1800mm2 and above cable copper segmentation single conductor shall not be less than 265  root.

The  surface of the conductor shall be smooth, free from oil pollution, no damage to  the shield and the insulation of the burr, sharp edge and a convex or broken  line;

4.2.2 Conductor Shielding and Insulation Shielding

The conductor shield should be composed of a semi conductive package and an extruded semi conductive layer, the thickness of which is 2.0mm, and the thickness of the extruded semi conductive layer is 1.5mm. The extruded semi conductive layer should be evenly coated on the semi conductive tape outside, and firmly adhered to the insulating layer. The semi conductive layer and the insulating layer of the interface should be smooth, no obvious strand, sharp corners, strand particles, burnt or scratches.

4.2.3 Insulation

Insulation material should be imported super purified to cross linked polyethylene material, its performance should be in accordance with the provisions of GB/Z 18890. The nominal thickness of the insulating layer shall be in accordance with the provisions of GB/Z 18890, The average thickness of the insulation and the nominal value shall be the positive tolerance, the positive tolerance is not greater than the nominal value of 10%+0.1mm.。

4.2.4 Insulation Shielding

The insulation shield is an extruded semi conductive layer, the thickness of which is similar to that of the 1.0mm insulation shield, which is evenly coated on the insulating surface and firmly adhered to the insulating layer. The surface of the insulation shielding and the interface between the insulation shield and the insulation layer should be smooth, with no sharp corners, particles, burnt or scratch marks.迹。

4.2.5 Waterproof Layer

The radial waterproof layer is advised to use the metal sleeve, or adopt the comprehensive waterproof layer. Insulation shield and the metal sleeve should be longitudinal resistance water structure, longitudinal resistance water structure should be semi conductive water resistance expansion tape wrapped into, semi conducting water-resistant tape should be wrapped tight, smooth and free of scratches.

4.2.6 Metal Shield

The  metal shielding are made by copper wire or copper tape or metal sleeve etc..
Metal shielding and metal sleeve section should meet the requirement of system short circuit capacity. When the section of the metal sleeve does not meet the requirements, it must be met by increasing the thickness of the metal sleeve or increasing the copper wire shielding.

4.2.7 Metal Sleeve

The metal sleeve may be a lead sheath or  wrinkle aluminum sleeve, and the wrinkle aluminum sleeve and lead sheath shall  comply with the provisions of GB/Z 18890. Lead should be used in accordance  with the provisions of JB/T 5268.2 lead alloy;
Wrinkle aluminum sleeve shall be made of  aluminum with a purity of not less than 99.6%, the elongation of aluminum strip  shall be not less than 16%. Welded corrugated aluminum sleeve shall not have circumferential direction of the weld, the inner wall of the weld shall be  flat, the strength of the weld shall be not less than the strength of the  aluminum cover, no obvious protrusion.

4.2.8 Asphalt Coating

Set of metal surface should be cable asphalt or hot melt adhesive anti-corrosion coating, anticorrosive coating on the metal sleeve layer should be good adhesion, complete and evenly, the bitumen cable should be in accordance with the provisions of SH 0001.。

4.2.9 Non Metallic Sheath

High density polyethylene (HDPE) and  polyvinyl chloride (PVC) materials should be used in the single layer jacket  structure. The performance, thickness and insulation level of the outer sheath shall  be in accordance with the provisions of GB/Z 18890, The surface should contain  a conductive layer which is not easy to fall off and good continuity, outer  sheath should have good anti-corrosion, anti ant, damp proof and flame  retardant properties; Low smoke and low halogen resistance fuel should be used  in the non metallic sheath of the cable in the tunnel. and combustion test  should be achieved national fire department approval of the test report.
The outer sheath to increase the "pest  control" ("Termigon") or "tuidi bug" anti termite  sheath,  should adopt double sleeve  structure,. The inner sheath should use high density polyethylene (HDPE) sheath  material, The outer jacket should be used "pest control" ("Termigon") or  "tuidi bug" anti termite sheath material.
The inner high density polyethylene sheath  thickness should be 3 ~ 3.5mm,  the outer sheath thickness should be 2 + 0.1mm. The inner high density polyethylene should  choose red additive, to show the difference between the outer layer and the anti  - ant sheath. The anti - ant sheath should have good corrosion resistance  (especially formic acid), wear resistance and elasticity. Surface should have a  high degree of finish.

5 Lifting, Storage and Transportation

5.1  Hoisting  cable applications meet the weight of crane and cable hoisting, prohibited  several dishes at the same time, hoisting, is strictly prohibited from throwing  height with cable of cable tray, non mechanical damage to the cables, lifting  shall not bump, oblique hanging and lifting points to correct, to light hanging  with care.
5.2 Cable tray does not allow flat or  rolling, cable accessories should avoid storing in the open air, cables and  accessories should avoid contact with corrosive substances, should take the  necessary precautions against fire. And there is a regular inspection, to  prevent accidents caused by cable and accessories damage.
5.3 Installed in vehicles, ships and other  means of transport of cable plate must be placed on a smooth, using appropriate  fixation methods (such as line tray) to prevent colliding or overturned.
5.4 The position of the cable tray (whether  or not there is no bracket) to be level, and shall not be stored on the  inclined plane of more than 5 degrees. Cable reel side superscript "cable  disc rolling direction" and "traction head out of the direction,  traction head out of the direction and the line direction, placed in front of the  line should be the confirmation.

Dimension and Weight Reference

Dimension and Weight Reference

Electrical Parameters

Electrical Parameters

Rating current of cable

Rating current of cable

Mechanical Parameters

Mechanical Parameters

Note: The above data is for reference only; if the data in the table does not conform to the National Standard, Please refer to the national standard of People's Republic of China.

    Guangzhou Nanyang cable Co. Ltd.

    No. 19 Yongfeng Road, Yonghe District, Guangzhou economic and Technological Development Zone, Guangdong, China

    © 2016 - 2017 NANYANG CABLE All Rights Reserved.

    CONTACT:

    National Sales:+86-13922732011

    FoShan Region:+86-18680032231

    TEL:+86-020-32206876

    FAX:+86-020-32208011

    E-MAIL:2685119216@qq.com gznycable@126.com

    网站备案:

    粤ICP备16116334号-3